Use

1. Open the activation switch, or activate the safety functionality that is wired to the STO
connection.
2. STO inputs on the drive control unit de-energize, and the drive control unit cuts off the
control voltage from the drive IGBTs.
3. The control program generates an indication as defined by parameter 31.22 (refer to
the firmware manual of the drive).
4. Motor coasts to a stop (if running). The drive will not restart while the activation switch
or safety relay contacts are open.
5. Deactivate the STO by closing the activation switch, or reseting the safety functionality
that is wired to the STO connection.
6. Reset any faults before restarting.
WARNING! The Safe torque off function does not disconnect the voltage of the
main and auxiliary circuits from the drive. Therefore maintenance work on
electrical parts of the drive or the motor can only be carried out after isolating the
drive from the main supply.
WARNING! (With permanent magnet or synchronous reluctance [SynRM] motors
only) In case of a multiple IGBT power semiconductor failure, the drive system
can produce an alignment torque which maximally rotates the motor shaft by
180/p (with permanent magnet motors) or 180/2p (with synchronous reluctance [SynRM]
motors) degrees regardless of the activation of the Safe torque off function. p denotes the
number of pole pairs.
Notes:
If a running drive is stopped by using the Safe torque off function, the drive will cut off
the motor supply voltage and the motor will coast to a stop. If this causes danger or is
not otherwise acceptable, stop the drive and machinery using the appropriate stop
mode before activating the Safe torque off function.
The Safe torque off function overrides all other functions of the drive.
The Safe torque off function is ineffective against deliberate sabotage or misuse.
The Safe torque off function has been designed to reduce the recognized hazardous
conditions. In spite of this, it is not always possible to eliminate all potential hazards.
The assembler of the machine must inform the final user about the residual risks.

Maintenance

After the operation of the circuit is validated at start-up, the STO function shall be
maintained by periodic proof testing. In high demand mode of operation, the maximum
proof test interval is 20 years. In low demand mode of operation, the maximum proof test
interval is 5 or 2 years; see section
dangerous failures of the STO circuit are detected by the proof test. To perform the proof
test, do the
Acceptance test procedure
Safety data (SIL, PL)
(page 245).
Safe torque off function 247
(page 248). It is assumed that all