Degree Of Protection Of Safur Resistors - ABB ACS880-07 Hardware Manual

45 to 710 kw, 50 to 700 hp
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Drive type
U
= 690 V
N
ACS880-07-0061A-7
ACS880-07-0084A-7
ACS880-07-0098A-7
ACS880-07-0119A-7
ACS880-07-0142A-7
ACS880-07-0174A-7
ACS880-07-0210A-7
ACS880-07-0271A-7
ACS880-07-0330A-7
ACS880-07-0370A-7
ACS880-07-0430A-7
ACS880-07-0470A-7
ACS880-07-0522A-7
ACS880-07-0590A-7
ACS880-07-0650A-7
ACS880-07-0721A-7
P
Maximum continuous braking power. The braking is considered continuous if the braking time
brcont
exceeds 30 seconds.
R
The minimum allowed resistance value of the brake resistor
min
R
Resistance value for the listed resistor assembly
E
Short energy pulse that the resistor assembly withstands every 400 seconds
R
P
Continuous power (heat) dissipation of the resistor when placed correctly
Rcont
The ratings apply at an ambient temperature of 40 °C (104 °F)

Degree of protection of SAFUR resistors

The degree of protection of SAFUR resistors is IP00.
Terminals and cable entry data
See section
Terminal and entry data for the power cables
Internal brake
chopper
P
R
brcont
min
kW
ohm
55
13
65
13
90
8
110
8
132
6
160
6
200
4
200
4
285
2.2
285
2.2
285
2
350
2
2xSAFUR125F500
350
2
2xSAFUR125F500
400
2
2xSAFUR125F500
400
1.8
2xSAFUR125F500
400
1.8
2xSAFUR125F500
Example brake resistor(s)
Type
SACE15RE13
SACE15RE13
SAFUR90F575
SAFUR90F575
SAFUR80F500
SAFUR80F500
SAFUR125F500
SAFUR125F500
SAFUR200F500
SAFUR200F500
SAFUR200F500
on page 210.
Resistor braking 257
R
E
P
R
Rcont
ohm
kJ
kW
13.0
435
2
13.0
435
2
8.0
1800
4.5
8.0
1800
4.5
6.0
2400
6
6.0
2400
6
4.0
3600
9
4.0
3600
9
2.7
3600
13
2.7
3600
13
3
3600
13
2
7200
18
2
7200
18
2
7200
18
2
7200
18
2
7200
18
3AXD10000044776