Control Unit Connection Data; Efficiency; Protection Classes; Ambient Conditions - ABB ACS880-07 Hardware Manual

45 to 710 kw, 50 to 700 hp
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Control unit connection data

Efficiency

Protection classes

Degrees of protection
(IEC/EN 60529)
Enclosure types (UL50)
Overvoltage category
(IEC/EN 60664-1)
Protective class
(IEC/EN 61800-5-1)

Ambient conditions

Installation site altitude
Air temperature
Relative humidity
See chapter
Control unit of frames R6 to R9
of frames R10 and R11
Approximately 98% at nominal power level
IP22, IP42, IP54
UL Type 1, UL Type 1 Filtered, UL Type 12. For indoor use only.
III
I
Environmental limits for the drive are given below. The drive is to be used in a
heated, indoor, controlled environment.
Operation
installed for stationary
use
0...2000 m (0...6562 ft)
above sea level. For
altitudes over 2000 m,
contact ABB.
Output derated above
1000 m (3281 ft). See
section Derating.
-0 to +40 °C (32 to
104 °F). No condensation
allowed.
Output derated in the
range +40 to +50 °C
(+104 to +122 °F). See
section Derating.
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
on page
on page 147.
Storage
in the protective package
-
-40 to +70 °C
(-40 to +158 °F)
Max. 95%
Technical data 219
137
or chapter
Control unit
Transportation
in the protective package
-
-40 to +70 °C
(-40 to +158 °F)
Max. 95%

Advertisement