Case 2: FSO-xx safety functions module above the control unit
Install the safety functions module next to the control unit as described below. Change the
original mounting plate of the module to the alternative plate included in the module
package.
WARNING! Obey the instructions in chapter
them, injury or death, or damage to the equipment can occur.
1. Stop the drive and do the steps in section
18
before you start the work.
2. Attach the FSO-xx safety functions module to the mounting plate with four screws.
3. Tighten the FSO-xx electronics grounding screw to tightening torque 0.8 N·m. Note:
The screw tightens the connections and grounds the module. It is essential for fulfilling
the EMC requirements and for proper operation of the module.
4. Connect the FSO-xx data cable to FSO-xx connector X110 and to connector X12 on
the control unit.
Safety
Precautions before electrical work
2
2
3
2
2
4
Electrical installation 135
instructions. If you ignore
on page
4