Checking incoming parameters in "Manual local" mode
The incoming parameters are checked as follows in "Manual local" mode:
● When the motor is switched off:
The motor starter saves the parameter and accepts it only when the motor starter has
switched over to "Automatic" mode again. Only after changing to "Automatic" are the
parameters checked.
● When the motor is running:
– The parameters are not accepted by the motor starter, even if the motor starter
– The "Parameters cannot be changed in ON state" diagnosis is set in data set 75
– The diagnosis "Group warning" is set.
– The motor is not switched off.
– A logbook entry is created
– The currently valid parameter values are retained.
4.6

Declaration of parameters

Load type
Here, you can specify whether the motor starter must protect a 1-phase load (direct-on-line
starters only) or a 3-phase load.
You will find more information in Chapter "Load type (Page 36)".
Trip class
The trip class (CLASS) specifies the maximum time within which a protective device must
trip from a cold state at 7.2 x the setting current (motor protection to IEC 60947).
You will find more information in Chapter "Overload protection (Page 42).
Thermal motor model (response to overload)
You use this device parameter to determine how the motor starter is to respond to overload.
You will find more information in Chapter "Overload protection (Page 42).
Response to CPU/master STOP
Determines the module's response to CPU STOP.
You will find more information in Chapter "Response to CPU STOP (Page 64)".
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002
changes later to "Automatic" mode.
(Page 124).
Parameters/address space
4.6 Declaration of parameters
95