Siemens SIMATIC ET 200SP Manual page 115

Motor starter (3rk1308-0**00-0cp0)
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Error type
channel
diagnostics
1022
134B
1093
1036
1040
1041
104C
1080
1083
1084
1088
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002
Fault text
Thermal motor model
h
overload
Trip reset not possible
h
Sensor supply overload
h
Receiving new safety-
n
related parameters (fail-
safe motor starters only)
Threshold I exceeded
h
Threshold I undershot
h
Motor blocking
h
Device fault
h
Switching element
h
overload
Electronics supply
h
voltage too low
No switching element
h
supply voltage
Remedial measures
The motor feeder has been overloaded. The motor
temperature rise has exceeded a limit.
Remedy: Please check the motor and the applications that
are being driven by the motor. After a trip, you can switch
the motor on again after the cooling time has expired, or
after the thermal motor model has been deleted.
Trip reset is currently not possible (e.g. because the cooling
phase is in progress).
Remedy: Repeat the action later (e.g. after the cooling time
has elapsed).
The output driver for the sensor supply is overloaded.
Remedy: Check the cabling and the sensor.
You have modified safety-related parameters. These have
not yet been confirmed.
The current has exceeded a limit.
Remedy: Please check the application that is being driven
by the motor.
The current has undershot a limit.
Remedy: Please check the application that is being driven
by the motor.
The maximum motor current has exceeded a limit for
blocking protection.
Possible cause: The motor is blocked.
Remedy: Please check the application that is being driven
by the motor.
Non-correctable fault detected following self-diagnostics
(contactor contacts, switching element, etc.).
Remedy: Check the logbook entries. If necessary, replace
the device.
Switching element (switching contact, power semiconductor)
too hot.
Check the ambient conditions linked to cooling. You might
have to take derating into consideration. Check the number
of switching operations. Also check whether the fan is
working properly.
The supply voltage is below the permissible value.
Remedy: Check the power supply (load measurement,
voltage range)
No supply voltage has been detected or the mechanical
rotary interlock is not in the READY position.
Remedy: Check the power supply to the switching elements
and the cabling or turn the mechanical rotary interlock to the
READY position.
Alarms/diagnostic messages
5.3 Interrupts
115