Substation monitoring

You can determine various system states with the help of the motor current and the current
limits.
System state
Motor operates more sluggishly,
e. g. due to bearing damage
Motor operates more smoothly,
e. g. because the system has run out of
processing material.
Motor is blocked
Open circuit
Defective fuse
Motor idling
Power failure
No load connected
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002
) 12 A motor starter at I
Off
= 10.4 A
= 8.6; thus: I
Startup
= 0.125 s T
≥ 19 s
Off
Current value
Current is higher than normal
Current is lower than normal
Very high current flowing
Very low current flowing
Minimum load undershot
Startup/
≈ 89 A