Circuit examples
B.2 Connection examples for fail-safe motor starters
B.2.3

Shutdown via a safety-related actuator via F-DQ

Article numbers:
● BaseUnit: 3RK1908-0AP00-0EP0
● Motor starter: 3RK1308-0C*00-0CP0 or 3RK1308-0D*00-0CP0
● F-DQ device: 6ES7136-6DB00-0CA0
To implement selective shutdown of one single motor starter, use a fail-safe F-DQ device or
the signal of a fail-safe sensor. The motor connected to the motor starter is shut down with a
direct connection of fail-safe sensors on the BaseUnit (BU30-MS6).
The sensor connected to the fail-safe digital input on the motor starter's BaseUnit requires
the same ground potential as the ground connection "M" on the motor starter's BaseUnit.