Siemens SIMATIC ET 200SP Manual page 87

Motor starter (3rk1308-0**00-0cp0)
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Note
Interrupted firmware update
If a firmware update has been interrupted, remove and reconnect the affected module before
a renewed firmware update.
Options for the firmware update
The following options are available for updating firmware:
● Online via PROFINET IO/PROFIBUS DP (with STEP 7)
● Via the integrated Web server (possible for CPU as well as centralized and distributed I/O
modules)
● With the TIA Portal:
– Non-fail-safe ET 200SP motor starter, SIMATIC STEP 7 V13 SP1 or higher with
– Fail-safe ET 200SP motor starter, SIMATIC STEP 7 V14 or higher with installed HSP
● Via a SIMATIC memory card
● With SIMATIC STEP 7 Version V5.5 SP4 or higher
Installation of the firmware update
Risk of impermissible system states
The CPU switches to STOP mode or the interface module to "station failure" as a result of
the firmware update being installed. STOP or station failure due to a firmware update can
cause an unpredictable motor starter state. After completion of the update, the current PIO
and the input actions take effect again.
Unexpected operation of a process or a machine can lead to fatal or severe injuries and/or
to property damage.
Before installing the firmware update, ensure that the motor starter, the CPU and the
interface module are not executing an active process.
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002
installed HSP
WARNING
Product overview
3.7 Functions
87