Product overview
3.7 Functions
3.7.22
Quick Stop clockwise
The action "Quick Stop CW" results in the following behavior:
● The motor is switched off with pending signal "Motor CW" without group fault
● The motor is not switched off with pending signal "Motor CCW"
● "Quick Stop CW" takes priority over "Motor CW"
● The input action responds to the active edge of the input signal, which means
deactivation is possible when the static input signal "Quick Stop" is present.
● The input trigger is reset through cancelation of the control commands "Motor CW" or
"Disable quick stop" (in the process image). This applies only in the case of control via
manual local mode or in the case of a retentive Quick Stop signal.
3.7.23
Quick Stop counter-clockwise
The action "Quick Stop CCW" results in the following behavior:
● The motor is switched off with pending signal "Motor CCW" without group fault
● The motor is not switched off with pending signal "Motor CW"
● "Quick Stop CCW" takes priority over "Motor CCW"
● The input action responds to the active edge of the input signal, Deactivation is possible
when the static input signal "Quick Stop" is present.
● The input trigger is reset through cancelation of the commands "Motor CCW" or "Disable
quick stop" (in the process image). This applies only in the case of control via manual
local mode or in the case of a retentive Quick Stop signal.
Note
No quick stop CW in the case of direct-on-line starters
You cannot use quick stop CCW in combination with direct-on-line starters.
78
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002