Siemens DI 8x24VAC/48VUC BA Manual
Siemens DI 8x24VAC/48VUC BA Manual

Siemens DI 8x24VAC/48VUC BA Manual

Digital input module

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for Siemens DI 8x24VAC/48VUC BA

  • Page 2 ___________________ Preface ___________________ Guide to documentation ___________________ SIMATIC Product overview ___________________ Wiring ET 200SP Digital input module ___________________ Parameter DI 8x24VAC/48VUC BA assignment/addressing (6ES7131-6CF00-0AU0) ___________________ Interrupts/diagnostics alarms Manual ___________________ Technical specifications ___________________ Parameter data record 07/2018 A5E42285997-AA...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    For environmentally friendly recycling and disposal of your old equipment, contact a certified electronic waste disposal company and dispose of the equipment according to the applicable regulations in your country. Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 5 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 6: Table Of Contents

    Status and fault displays ......................18 Interrupts ..........................20 Diagnostics alarms ........................20 Technical specifications ........................21 Parameter data record .......................... 24 Parameter assignment and structure of parameter data record ..........24 Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 7: Guide To Documentation

    SIMATIC ET 200SP. distributed I/O system. The STEP 7 online help supports you in the configuration and programming. Device information Product manuals contain a compact description of the module-specific information, such as properties, wiring diagrams, characteristics and technical specifications. Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 8 You need to register once to use the full functionality of "mySupport". You can find "mySupport" in the Internet (https://support.industry.siemens.com/My/ww/en). "mySupport" - Documentation In the Documentation area of "mySupport", you have the possibility to combine complete manuals or parts of them to make your own manual.
  • Page 9 With the TIA Selection Tool, you can generate a complete order list from your product selection or product configuration. You can find the TIA Selection Tool on the Internet (http://w3.siemens.com/mcms/topics/en/simatic/tia-selection-tool). Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 10 You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/98161300). PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the plant network during commissioning. PRONETA features two core functions: ● The topology overview independently scans PROFINET and all connected components.
  • Page 11 Guide to documentation SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
  • Page 12: Product Overview

    Color code for selecting the color identification labels ⑤ ⑫ LEDs for channel status BU type ⑥ ⑬ LED for supply voltage Article number ⑦ Function class Figure 2-1 View of the module DI 8x24VAC/48VUC BA Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 13 ● Labeling strips ● Color identification labels ● Reference identification label ● Shield connector You can find additional information on the accessories in the ET 200SP Distributed I/O System (https://support.industry.siemens.com/cs/ww/en/view/58649293) system manual. Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 14: Wiring

    Wiring Wiring and block diagram This section includes the block diagram of the DI 8x24VAC/48VUC BA module with the terminal assignments for a 1-wire and 2-wire connection. Information about wiring of the BaseUnit is available in the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293).
  • Page 15 3.1 Wiring and block diagram Connection: 1-wire and 2-wire connection The following figure shows the block diagram and an example of the terminal assignment of the digital output module DI 8x24VAC/48VUC BA on the BaseUnit BU type U0 (1-wire and 2-wire connection). ①...
  • Page 16: Parameter Assignment/Addressing

    (module plugged into a dark-colored Ba- seUnit) Enable new potential • group (module plugged into light- colored BaseUnit) The parameter length of the I/O module is 3 bytes. Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 17: Explanation Of Parameters

    You take the potential of the self-assembling voltage buses P1, P2 and AUX from the left neighbor. A potential group ends with the dark-colored BaseUnit, which is followed by a light-colored BaseUnit or server module in the station configuration. Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 18: Address Space

    V15 with HSP 0254 Address space of the digital input module DI 8x24VAC/48VUC BA The figure below shows the assignment of the address space for DI 8x24VAC/48VUC BA. Figure 4-1 Address space of the digital input module DI 8x24VAC/48VUC BA...
  • Page 19: Interrupts/Diagnostics Alarms

    The figure below shows the LED displays (status and error displays) of the DI 8x24VAC/48VUC BA. ① DIAG (green/red) ② Channel status (green) ③ PWR (green) Figure 5-1 LED display Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 20 Process signal = 0 Off
 Process signal = 1 LED PWR Table 5- 3 LED PWR status display LED PWR Meaning No supply voltage L Off
 Supply voltage L present Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 21: Interrupts

    Interrupts/diagnostics alarms 5.2 Interrupts Interrupts The DI 8x24VAC/48VUC BA digital input module supports diagnostics interrupts. Diagnostic interrupts The module generates a diagnostic interrupt at the following events: ● Parameter assignment error ● No supply voltage Diagnostics alarms A diagnostic alarm is generated and the DIAG-LED flashes on the module for each diagnostics event.
  • Page 22: Technical Specifications

    70 mA; without sensor supply Encoder supply Number of outputs Short-circuit protection Yes; Per module, 5x 20 mm fuse, 2 A/250 V, quick-response, replaceable Output current up to 60 °C, max. • Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 23 15 ms – at "0" to "1", max. 20 ms – at "1" to "0", max. Cable length 1 000 m shielded, max. • 600 m unshielded, max. • Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 24 1 200 V DC between supply voltage and back- plane bus Dimensions Width 20 mm Height 73 mm Depth 58 mm Weights Weight, approx. 40 g Dimensional drawing See the manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/59753521) Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 25: Parameter Data Record

    However, a corresponding error code is written to the STATUS output parameter. The description of the "WRREC" instruction and the error codes is available in the STEP 7 online help. Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 26 Channel 0 includes the diagnostics enable for the entire module. Figure A-1 Structure of data record 128 Header information The figure below shows the structure of the header information. Figure A-2 Header information Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...
  • Page 27 WRREC instruction. Wrong version or error in the Correct the version, length and number of header information. parameter blocks. Invalid coding for input filter time. Check the parameters of the module. Digital input module DI 8x24VAC/48VUC BA (6ES7131-6CF00-0AU0) Manual, 07/2018, A5E42285997-AA...

This manual is also suitable for: