Configuring ATEX operation

ET 200SP fail-safe motor starters protect motors in an ATEX environment. The following
parameters are considered to be safety-related in ATEX operation:
● Rated operating current (I
● Trip class
You set the parameters via the data sets or using the engineering software.
Before the new safety-related parameters are accepted, however, check and confirm the
new parameters. The parameter settings are indicated by means of a flashing sequence of
the LEDs on the fail-safe motor starter. As soon as you have ensured with the aid of the
LEDs that all parameters are correctly set, confirm the new parameters on the device by
means of the blue button. The parameters are not accepted until you have confirmed and the
motor starter is "Ready for motor ON". Changes to parameters that are not safety-related do
not require confirmation.
100
)
e
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002