Product overview
3.7 Functions
n action
Motor CW
Motor CCW
(with
reversing
starters only)
Quick Stop
Quick Stop
clockwise
Quick Stop
counter-
clockwise
Trip RESET
Cold start
Operational
trip end
position CW
68
Input
Input
Input
n level
n signal
NO
n. ret./ret.
NO/NC
n. ret./ret.
NO/NC
n. ret./ret.
NO/NC
n. ret./ret.
NO
n. ret.
NO
n. ret.
NO/NC
n. ret.
Operating
mode
Manual
The motor starter must be in "manual local"
•
mode
mode for these actions.
local
Motor CW: Switching the motor on or off
•
Motor CCW: Switching the motor on or off
•
Only allowed as an NO contact
•
n. ret. The input action is active while the
•
input signal is pending.
ret.: The action becomes active by means of
•
the rising edge of the input and remains active
regardless of the level. The action is reset by
the input action "Quick Stop" or "group fault".
All
Motor is switched off direction-independently
•
without group fault.
"Quick Stop" takes priority over "Motor CW"
•
and "Motor CCW"
All
Motor is switched off with "Motor CW" without
•
group fault.
"Quick Stop" takes priority over "Motor CW"
•
All
Motor is switched off with "Motor CCW"
•
without group fault.
"Quick Stop" takes priority over "Motor CCW"
•
The action is only available for reversing
•
starters.
All
"Trip RESET" is triggered once.
•
"Trip RESET" is only possible as NO contact.
•
All
Enables switch-on without main power. If the
•
main power supply is nevertheless present
(current flowing), an internal trip command is
generated.
Cannot be set in the case of fail-safe motor
•
starters
All
The motor is tripped regardless of the direction of
rotation (CW or CCW).
The motor can only be switched on with
•
"Motor CCW".
The parameter can only be implemented as
•
"non-retentive".
A group fault is not generated, but a
•
diagnostics message is set in data set 92.
Manual, 12/2016, A5E34821005002A/RS-AB/002
Description
Motor starter (3RK1308-0**00-0CP0)