The supported object numbers and their meanings are shown in the table below: in the case
of standard motor starters, you can acknowledge faults by switching off the supply voltage
and by switching it on again. Replace the motor starter if the fault occurs again. In the case
of fail-safe motor starters, there are some faults that you cannot acknowledge. Always
replace the fail-safe motor starter if the relevant message in the "Fail-safe motor starter
defective" column is marked with an "x".
Table A- 1
Object No. Device fault messages
308
417
418
437
456
458
460
464
476
478
479
480
486
487
490
1414
1417
1466
1467
381
1407
1482
20010
20011
20012
20013
20015
20017
Motor starter (3RK1308-0**00-0CP0)
Manual, 12/2016, A5E34821005002A/RS-AB/002
Assignment of object number to device error message
Switching element defective
Stack overflow
Stack underflow
Watchdog overflow
EEPROM: memory defective
EEPROM: CRC error "Device parameter"
EEPROM: Contains invalid data
ROM error
Current measuring defective
Bypass element does not close
Bypass element does not open
Bypass element protection has opened unintentionally during
operation
Program execution check: Sequential program execution error
Program execution check: Logical programming error
Incorrect power section detected
Switching element short-circuited
Bypass element defective
Contact 1 failed
Contact 2 failed
Self-test error
Electronics supply voltage too high
Current measuring range overshot
Direct-on-line or reversing relay defective
(Available for fail-safe motor starters only)
12 V power supply defective
(Available for fail-safe motor starters only)
F-DI defective
(Available for fail-safe motor starters only)
Hard switching of relays
(Available for fail-safe motor starters only)
Relay control defective feedback message
(Available for fail-safe motor starters only)
Residual current detection or bypass element does not close
A.2 DS72 logbook - Read device error
Fail-safe motor starter
Data sets
defective
x
-
-
-
x
x
-
x
x
-
x
-
-
-
-
x
x
x
x
-
-
x
x
x
x
x
x
-