Advertisement

1MRK 511 245-UUS -
4.6.1
650 series ANSI
Engineering Manual
Procedure to insert a configured IED in 650 series
1.
Right-click the bay and select Import ... to select the IED configuration file
(*.pcmi) , see
Figure
IEC09000644 V1 EN
Figure 25:
Import an IED from the context menu
2.
Import the *.pcmi file from the bay level in the plant structure.
3.
Click OK to insert the new IED object in the plant structure.
4.
Modify the configuration according to the needed application.
5.
Write the configuration to the IED.
Ordered default configurations are not locked. The user can use any of
the available default configurations for a particular product type as a
base to create an own configuration. The only requirement is that all
needed hardware and software options are available.
It is possible to give the inserted IED in the plant structure a user
defined name. Be sure to only user characters a-z, A-Z, 0-9 and _. Do
not use space character in IED names.

Setting IED IP address in the project

There are two alternatives to set IP address of the IED object in PCM600. The IED
object in PCM600 must have the same IP address and subnetwork mask as the front or
25.
IEC09000644-1-en.vsd
Section 4
Setting up a project
47