Section 6
Local HMI engineering
76
LED operation mode LatchedAck-S-F
This operation mode operates exactly as the one described above (LatchedAck-F-S).
The only difference is that the illumination mode is changed. Flash mode instead of
steady mode and steady mode instead of flash mode.
LED operation mode LatchedColl-S
R
Y
G
R
Y
G
Reset LED
Illumination =>
= Steady
= Flash
IEC08000402 V1 EN
Figure 50:
LHMI: LED operation mode LatchedColl-S
This mode catches a signal change to ON and the LED stays ON until the operator
resets the LEDs for this group.
If the signal is still ON when a reset LED is done, the LED will illuminate again. This
occurs when the application configuration accesses the signal again in the next cycle
after reset. The thin dashed lines in
following the signal and reset, when no higher prior signal is given.
The LED illuminates always in steady mode.
IEC08000402.vsd
Figure 50
shows the internal state of the LED
1MRK 511 245-UUS -