BIO
TRM
GOOSE Inputs
IEC08000173 V2 EN
Figure 39:
SMT: Operation principles
A binary input channel can be connected to one or several function block inputs, see
Figure
40. If a binary input channel is connected to several different function blocks in
ACT, the connection will appear as glue logic in SMT.
A binary output channel can only be activated from one function block output. If it
should be activated from more than one function block output, glue logic has to be
used. Glue logic means inserting a logical gate (OR and AND blocks) between the
function blocks and the binary output channel. This can be engineered in SMT.
Connections made in SMT are automatically shown in ACT.
Connections made in ACT are automatically shown in SMT.
Protection and control engineering
FBs
FBs
SMAI
GOOSE FBs for
IEC 61850
binary and analog
data, interlocking
communication
and voltage control
IEC08000173_2_en.vsd
Section 5