ABB 650 series ANSI Engineering Manual page 87

Hide thumbs Also See for 650 series ANSI:
Table of Contents

Advertisement

1MRK 511 245-UUS -
650 series ANSI
Engineering Manual
IEC08000127 V1 EN
Figure 54:
GDE: Dynamic Text symbols
The standard (IEC or ANSI) for the symbols and the selection of the font size for the
text elements can be changed using the two selector boxes on top of the page window.
HMI display raster layout and text font selection
The raster in the page changes from symbol presentation to text presentation when a
text object is selected and vice versa.
The text can be presented in two different font sizes:
UniCode characters (6 x 12 pixel), or
UniCode characters (13 x 14 pixel)
The total size of the presented white area (page) represents the visible part of the local
HMI display without header and foot-line.
The visible display for a single line diagram is organized in a raster of 13 x 8 (columns
x rows). Each symbol -presented by 24 x 24 pixels- included by the drag and drop
method must be dropped in a raster box. The icon Snap to grid must be enabled to
place a symbol. The description text for an apparatus object can be placed in all four
directions around the symbol. The description is part of the apparatus object. It is
possible to place the symbols not under assistance of Snap to Grid.
Handling text
The raster switches when text is selected in a raster of 45 x 15 (columns x rows). One
raster box is the placeholder for one character. A text element must be placed in the
position of the raster. The name and the unit of a measurement or text symbol can be
changed either by double click the symbol or via the object property window.
Select and toggle Show Texts using the IED Fonts to get a view how it will look like
later on the real HMI display.
Local HMI engineering
IEC08000127.vsd
Section 6