Setting Up Communication Between Pcm600 And The Ied - ABB RET670 Commissioning Manual

Transformer protection version 2.1 ansi
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK 504 154-UUS B
1
0
IEC04000310 V2 EN-US
Figure 2:
1 IED energized. Green LED instantly starts flashing
2 LCD lights up and "IED startup" is displayed
3 The main menu is displayed. A steady green light indicates a successful startup.
If the upper row in the window indicates 'Fail' instead of 'Available' and the green LED flashes, an
internal failure in the IED has been detected. See
to investigate the fault.
4.5

Setting up communication between PCM600 and the IED

The communication between the IED and PCM600 is independent of the communication protocol
used within the substation or to the NCC.
The communication media is always Ethernet and the used protocol is TCP/IP.
Each IED has an RJ-45 Ethernet interface connector on the front. The front Ethernet connector
shall be used for communication with PCM600.
When an Ethernet-based station protocol is used, PCM600 communication can use the same
Ethernet port and IP address.
To connect PCM600 to the IED, two basic variants must be considered.
Direct point-to-point link between PCM600 and the IED front port. The front port can be seen
as a service port.
Indirect link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to enable
communication.
The communication procedures are the same in both cases.
1.
If needed, set the IP address for the IEDs.
2.
Set up the PC or workstation for a direct link (point-to-point), or
3.
Connect the PC or workstation to the LAN/WAN network.
4.
Configure the IED IP addresses in the PCM600 project for each IED to match the IP addresses
of the physical IEDs.
Setting up IP addresses
The IP address and the corresponding communication subnetwork mask must be set via the LHMI
for each available Ethernet interface in the IED. Each Ethernet interface has a default factory IP
Commissioning manual
2
t1
xx04000310-1-en.vsd
Typical IED start-up sequence
3
t (s)
t2
section"Checking the self supervision function"
Section 4
Starting up
SEMOD58570-5 v12
41