Goose Data Exchange - ABB 650 series ANSI Engineering Manual

Hide thumbs Also See for 650 series ANSI:
Table of Contents

Advertisement

Section 7
IEC 61850 communication engineering
7.1.2.1
94
FBs
FBs
GOOSE
GOOSE
Receive
LN
Receive
LN
GOOSE
GOOSE
Send
Send
FB
FBs
AFL
with
monitoring
LN
only
part
FB
AFL
FBs
LN
with
part
monitoring
and
commands
FB
AFL
LN
part
IEC08000364 V1 EN
Figure 60:
IEC 61850: Communication interface principle
IEC 61850 has as a concept for the identification of all signals for communication that
belong to a function by a logical node as a placeholder. All signal information in
command and monitoring direction, which belongs to a function, is available within
the logical node.
Whenever a function block is instantiated in ACT, PCM600 automatically generates
the corresponding logical node data. In
function block. The upper part is the visible function block in ACT and the lower part
is the logical node data for the function block.

GOOSE data exchange

The IEC 61850 protocol supports a method to directly exchange data between two or
more IEDs. This method is described in the IEC 61850–7–2 clause 15. The concept is
based on sending a multicast over the Ethernet. Whoever needs the information detects
GOOSE
Receive
GOOSE
Send
Commands
Event
handler
Event
queue
Figure 60
this is shown by two parts per
1MRK 511 245-UUS -
IEC08000364.vsd
650 series ANSI
Engineering Manual

Advertisement