ABB 650 series ANSI Engineering Manual page 78

Hide thumbs Also See for 650 series ANSI:
Table of Contents

Advertisement

Section 6
Local HMI engineering
72
The LED illumination follows the status of the signal. The LED illuminates
flashing (F).
LatchedAck-F-S
The LED latches the signal change OFF-ON and flashes (F) until it is
acknowledged.
When the signal is still ON at the time the signal is acknowledged the LED
changes to steady (S) mode.
When the signal has already changed to OFF before the time it is
acknowledged, the LED turns to OFF.
LatchedAck-S-F
The same as LatchedAck-F-S but the LED starts with steady state and
flashes after acknowledgment.
LatchedColl-S
The LED illuminates in all cases in steady mode only
The LED latches a signal change from OFF-ON until it is acknowledged by
the operator.
The LED stays in steady mode when it is reset and the signal is still in ON
state.
The LED is OFF only after the signal has changed to OFF state AND it is
reset by the operator via 'Clear' operation.
LatchedReset-S
This mode is used for all LEDs that are used to indicate a disturbance. The
LEDs will stay in the last state after the disturbance run time until they are
reset after a defined time.
The timers are set in Parameter Setting tool in the function block LEDGEN.
IEC09000657 V1 EN
Figure 44:
LHMI: LED operation mode
1MRK 511 245-UUS -
IEC09000657-1-en.vsd
650 series ANSI
Engineering Manual