1MRK 511 245-UUS -
Section 2
2.1
650 series ANSI
Engineering Manual
Engineering tool set
Introduction
The structure of a monitoring and control system for electrical substations has a
principle structure as shown in
purposes.
For performance reasons, do not insert more than 65 IEDs of 650 series
type in one PCM600 project. Larger projects can be divided into
several PCM600 projects.
It can be subdivided in the three main parts:
•
Bay level IEDs
•
Station communication
•
Station level IEDs
NCC-GW
HSI
(station-IED1)
(station-IED2)
bay
bay
IED 1
IED 2
IEC08000101 V1 EN
Figure 2:
Principle structure of a monitoring and control system for a substation
All three parts require specific engineering and configuration. PCM600 is used to do
the complete engineering and configuration activities needed for bay level IEDs.
Figure
2. It contains a number of IEDs for the various
PCM600
(tool set)
Station bus
bay
bay
IED n-1
IED n
Section 2
Engineering tool set
Station level
Station
Communication
Bay level
IEC08000101.vsd
17