Writing Communication Configuration To Ied - ABB 650 series ANSI Engineering Manual

Hide thumbs Also See for 650 series ANSI:
Table of Contents

Advertisement

1MRK 511 245-UUS -
7.6
650 series ANSI
Engineering Manual
1.
Select an existing IED to import IEC 61850 files.
2.
Select the file type of IEC 61850 to import from the Files of type drop down list
(ICD or CID)
3.
The SCL Import Option menu opens, which queries how the file should be handled
during import, see
Figure
3.1. Ignore Substation Section will not import the "SSD-file" part of the SCD-file.
3.2. Don't import ... protects the existing IEDs in case the SCD file does not
match the original configuration in PCM600.
3.3. Replace unknown ... can be used when it is known that the file includes
additional IEDs which are needed. The IED of type Generic IEC 61850 IED
is used to integrate these kinds of IEDs in for example the plant structure.
3.4. Click Ignore PCM Object Type to update the IED object(s) in PCM600 from
the IED type(s) in the SCD file, disregarding if the IED type(s) in the SCD
file matches the IED object(s) in PM600 or not.
3.5. Start Import when the definition has been completed. A progress window
presents the import procedure.
4.
IEC09000631-1-en.vsd
IEC09000631 V1 EN
Figure 71:
IEC 61850: SCL Import option

Writing communication configuration to IED

IEC communication depends on proper communication configuration in all IEDs that
communicate via IEC 61850. It is not possible to read the communication
configuration from the IED to PCM600.
However it is possible to make a configuration change in one IED, without affecting
the communication engineering. For example, when the Application Configuration tool
IEC 61850 communication engineering
71.