Section 6
Local HMI engineering
70
The 15 LEDs on the right side of the LCD can indicate in total 45 alarms,
warnings or other signals to the operator. They are organized in three groups 1 to 3.
Each signal group belongs to one function block.
Each LED illuminates in one of the three colors: RED, YELLOW or GREEN.
The organization of flashing, acknowledgment and group selection is done directly
between the function blocks and the basic LHMI keys, the 'Multifunction' key [a]
to toggle between the three groups or the 'Clear' key [b] to acknowledge or reset
the LEDs.
Only the programming of the signals is needed for the LEDs.
The operation mode of the LEDs is defined in Parameter Setting tool.
Function block FNKEYMD1 to 5
Every function key has an own FNKEYMD function block.
The 5 function keys on the left side of the LCD [B] can be used to process demands.
The function block handles the signal for the LED included in the key as input signals.
The LED signal of the key is independent of the key function and must be
programed to process demands.
The function block handles the operators command when the key is pressed as
output signal.
The functions are activated whenever a key is pressed the first time. The
corresponding text elements for the five keys appear on the left side of the LCD.
No execution of the function is done. So the first push is used to activate the
presentation only.
The next key push is handled as activate function and the output signal of the
function block is set.
The operation mode of the function key is defined in Parameter Setting tool (pulse,
toggle).
Parameter Setting tool and function block configuration
The operation mode of the function keys and the LEDs must be defined per key and
LED in Parameter Setting tool.
The function key can operate as:
Pulsed signal
Each push forces a pulse of a configured time.
The pulse time can be set in Parameter Setting tool.
The default pulse time is 200 ms.
Toggle signal
1MRK 511 245-UUS -
650 series ANSI
Engineering Manual

Advertisement