Connectors - Kollmorgen AKD series Installation Manual

Hide thumbs Also See for AKD series:
Table of Contents

Advertisement

7.11 Connectors

AKD-xzzz06 and AKD-xzzz07 types
Connector
Control signals X7/X8
Control signals X21/X22* Terminal Connector, 8 poles
Control signals X23/X24* Terminal Connector, 14 poles 1.5 mm², 16 awg 10 A
Control signals
X35/X36**
Feedback X10
Service Port X11, X32**
Motion Bus X5, X6
CAN In/Out X12/13
Encoder Emulation X9
* with I/O option card "IC" only
** with AKD-M variant only
AKD-xzzz06 types (120V to 240V Mains Voltage Supply)
Connector
24V/STO X1 (03 to 24A)
Motor X2 (3 to 6 A)
Motor X2 (12 to 24 A)
Power/Regen X3 (3 to 6A) Terminal Connector, 7 poles 2.5 mm², 14 awg 10 A
Power/Regen X3 (12 A)
Regen X3 (24 A)
Power X4 (24 A)
AKD-xzzz07 types (240V to 480V Mains Voltage Supply)
Connector
24V/STO X1 (03 to 24A)
24V/STO X1 (48A)
Motor X2 (03 to 24A)
Motor X2 (48A)
Regen X3 (03 to 24A)
Regen X3 (48A)
Power X4 (03 to 24A)
Power X4 (48A)
DC-Bus X14 (48A)
24V Brake X15 (48A)
Brake X16 (48A)
1
single-line connection
2
single-line connection with recommended conductor cross section (➜ # 42)
3
rated voltage with pollution level 2 (lowest values according to UL840 and IEC60664)
AKD Installation | 7   Technical description and data
Type
Terminal Connector, 10 poles 1.5 mm², 16 awg 10 A
Terminal Connector, 8 poles
SubD 15pin HD (female)
RJ45
RJ45
RJ25
SubD 9pin (male)
Type
Terminal Connector, 3 poles 1.5 mm², 16 awg
Terminal Connector, 6 poles 2.5 mm², 14 awg 10 A
Terminal Connector, 6 poles 10 mm², 8 awg
Terminal Connector, 8 poles 2,5 mm², 14 awg 16 A
Terminal Connector, 4 poles 10 mm², 8 awg
Terminal Connector, 4 poles 10 mm², 8 awg
Type
Terminal Connector, 3 poles
Terminal Connector, 8 poles
Terminal Connector, 6 poles
Terminal Connector, 4poles
Terminal Connector, 4 poles
Terminal Connector, 3 poles
Terminal Connector, 4 poles
Terminal Connector, 4 poles
Terminal Connector, 3 poles
Terminal Connector, 2 poles
Terminal Connector, 2 poles
Kollmorgen | kdn.kollmorgen.com | October 2017
Max. Cross
Current
Voltage
1
2
Section
1.5 mm², 16 awg 10 A
1.5 mm², 16 awg 10 A
0,5 mm², 21 awg
1 A
0,5 mm², 21 awg
1 A
0,5 mm², 21 awg
1 A
0,5 mm², 21 awg
1 A
0,5 mm², 21 awg
1 A
Max. Cross
Current
Voltage
1
2
Section
8 A
30 A
30 A
30 A
Max. Cross
Current
Voltage
1
2
Section
1.5 mm², 16 awg
8 A
1.5 mm², 16 awg
8 A
10 mm², 8 awg
30 A
16 mm², 6 awg
54 A
10 mm², 8 awg
30 A
16 mm², 6 awg
54 A
10 mm², 8 awg
30 A
16 mm², 6 awg
54 A
16 mm², 6 awg
54 A
1.5 mm², 16 awg
8 A
1.5 mm², 16 awg
8 A
3
250 V
250 V
250 V
250 V
<100 V
<100 V
<100 V
<100 V
<100 V
3
160 V
320 V
1000 V
320 V
320 V
1000 V
1000 V
3
160 V
160 V
1000 V
1000 V
1000 V
1000 V
1000 V
1000 V
1000 V
160 V
160 V
41