External Battery Cabinet And Battery Connection; External Battery Configuration - ABB CONCEPTPOWER CLASSIC DPA-50 User Manual

Conceptpower dpa series
Table of Contents

Advertisement

2.3.2 EXTERNAL BATTERY CABINET AND BATTERY CONNECTION

WARNING!
2.3.2.1

External Battery Configuration

In the UPS-cabinet of the Conceptpower DPA
batteries.
There are 2 external matching battery cabinets available:
CBAT DPA-120 for Separate or Common battery configurations of 24Ah or 28Ah blocks
CBAT DPA-200 for Separate or Common battery configurations for 24Ah or 28Ah blocks
S-type = For Separate. Battery
C-type = For Common. Battery
BATTERY FRAMES
Configuration accommodates:
Battery fuses / Max. Batt. Strings :
Terminals :
Battery fuses / Max. Batt. Strings
Terminals :
Fuse Type (Very Fast acting)
Dimensions (WxHxD)
Weight with trays and w/o
batteries
For detailed information and layout of the battery cabinets please refer to section 10 / Options
KEEP OUT OF BATTERY POLES WHICH CONTAIN DANGEROUS DC-VOLTAGES
CAUSING FATAL ACCIDENTS.NOTE:
MANIPULATION ON THE BATTERY SYSTEM SHOULD ONLY BE DONE BY
TRAINED SERVICE AND MAINTENANCE PERSONEL OF THE MANUFACTURER
OR HIS AUTHORISED SERVICE PARTNERS. INAPPROPRIATE MANIPULATIONS
OF THE BATTERIES CAN CAUSE LIGHTNING SPARKS. WHILE OPERATING ON
BATTERY SYSTEMS IT IS MANDATORY TO WEAR GLASSES.
TM
S2 UPGRADE DPA 250 there is no space provided for
CBAT-DPA-120
120 Batt. block x 24Ah/28Ah
Max.
3x5=15 blocks/shelf
S-type
(Terminal 9 x 16/25mm2)
C-type
+ Com. Connection Bar
3 x (2xM8) +PE 2xM8
A
mm
kg
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202
Printed in Switzerland – Modifications reserved
S-type or C-type
on 8 shelf
3 / 3
3 / 3
3x100 A
730x1975x800
290
Section-2
(max. 120 Blocks)
(max. 200 Blocks)
CBAT-DPA-200
S-type or C-type
200 Batt. blocks x
24Ah/28Ah
on 7 shelf
6x5=30 blocks/shelf
5 / 5
(Terminal 15 x 16/25mm2)
5 / 5
+ Com. Connection Bar
3 x (2xM10) +PE 2xM10
5x100A
1200x1975x800
410