Jd11 / Rs232 Computer Interface; Jd12 / Rs232 Interface For Multidrop; Usb/2 Computer Interface - ABB CONCEPTPOWER CLASSIC DPA-50 User Manual

Conceptpower dpa series
Table of Contents

Advertisement

On the Interface board are located two LED's:
Green LED showing the status of the Interface:
Red LED
On the Master board the following ports are active:
The Input ports (X1)
The Output port (X2, X3, X4)
On the Salve boards the following parts are active.
The Output ports X3/6 ... X3/10 and X4/1 ...X4/10 (Means Alarm . Module 1 , 2, 3 ,4, 5)
All other input or output ports on the Slave boards are not activated.

3.1.3 JD11 / RS232 Computer Interface

The Computer Interface JD11 (4) located on the distribution part is an intelligent RS 232 serial port that allows
the UPS system to be connected to a computer. The connector JD11 is a standard D-Type, 9-pin, female.
When installed the Computer Interface, the optional WAVEMON software allows the computer to monitor the
mains voltage and the UPS system status continuously.
In the event of any changes the computer terminal will display a message.
(For details see our optional Monitoring Package: WAVEMON).
3.1.4

JD12 / RS232 Interface for Multidrop

The Computer Interface JD12 (5) located on the distribution part is an intelligent RS232 serial port that allows to
get from several UPS cabinets which are connected in parallel the complete system information by using the
Multidrop connection kit. (For details see user manual Multidrop kit). The connector JD12 is a standard D-Type, 9-
pin, male.
3.1.5

USB/2 Computer Interface

The Computer Interface USB (6) located on the distribution part and is in parallel with the intelligent
RS 232 serial port JD11.
When installed the USB Computer Interface trough, the optional WAVEMON software allows the computer to
monitor the mains voltage and the UPS system status continuously.
In the event of any changes the computer terminal will display a message.
(For details see our optional Monitoring Package: WAVEMON).
Fig. 3. Example : Distribution Interfaces
- Fast Blinking: 2 times/sec = Interface is Master (1
- Slow Blinking: 1 times/sec = Interface is Slave ( 2
Board Alarm (indicates a possible replacement of the board)
04-3008_S3_ABB_OPMCPDPA-S2_GB_121202
Printed in Switzerland – Modifications reserved
st
nd
1
1
X1-X4 Customer interface on Phoenix Terminals:
2
X1 Customer Inputs
3
X2...X4 = Outputs Potential free contacts
2
SW1-9
3
JD8
4
ONLY For paralleling cabinets use optional adapter:
JD5
5
JD6
6
4
JD11
5
JD12
6
USB
7
7
SNMP
Cabinet of a parallel System)
th
,.. 5
cabinet of a //- System)
Multi-Cabinet Configuration Switch
Parallel BUS connector
Parallel BUS - Input Connector
Parallel BUS - Output Connector
RS232 / Sub D9/ female, PC interface
RS232/ Sub D9 / male for Multidrop ONLY
PC Interface
Slot for optional SNMP card ONLY
Page 4/4 ABB
Section-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents