10.12 WIRING AND BLOCK DIAGRAMS FOR ALL FRAMES AND MODULES
The customer has to supply the wiring to connect the UPS to the local power source. The installation inspection
and initial start up of the UPS and extra battery cabinet must be carried out by a qualified service personnel such
as a licensed service engineer from the manufacturer or from an agent authorised by the manufacturer.
More details and procedure are mentioned in the user manual.
10.12.1 TERMINAL CONNECTIONS OVERVIEW
FRAME TYPE
Separate. Battery
Terminals (T)
Connection Bar (B)
CLASSIC DPA-50
3+1 x 16/25mm
9+1 x 16/25mm
TRIPLE DPA-150
+PE 1xM10 (B)
15 x 16/25mm
UPGRADE DPA-250
+PE 1xM12 (B)
CLASSIC DPA-50
TRIPLE DPA-150
UPGRADE DPA-250
Dual feed input
Common Battery
(+ / N / - ) +PE
(+ / N / - ) +PE
2
(T)
3+1 x 16/25mm
2
(T)
3 x M10 (B)
+PE 1xM10 (B)
2
(T)
3 x M12 (B)
+PE 1xM12 (B)
Single feed input
04-3008_S10_ABB_TDSCPDPA-S2_GB_121202
Printed in Switzerland – Modifications reserved
Input Bypass
Input Rectifier
3+N
2
2
(T)
4 x 16/25mm
(T)
5 x 16/25mm
3 x M10(B)
+PE 1xM10 (B)
+PE 1xM10 (B)
3 x M12 (B)
+PE 1xM12 (B)
+PE 1xM12 (B)
Output load
3+N+PE
3+N+PE
2
(T)
5 x 16/25mm
4 x M10 (B)
4 x M10 (B)
+PE 1xM10 (B)
4 x M12 (B)
4 x M12 (B)
+PE 1xM12 (B)
Section-10
2
(T)
Page 17/19 ABB