Led Indicators; Keys; On/Off Start-Up And Shutdown Buttons - ABB CONCEPTPOWER CLASSIC DPA-50 User Manual

Conceptpower dpa series
Table of Contents

Advertisement

Load transfer from INVERTER to BYPASS and vice-versa;
DIAGNOSIS (SERVICE MODE);
Adjustments and testing.

4.1.2.2 LED Indicators

The mimic diagram serves to indicate the general status of the UPS. The LED-indicators show the power flow
status and in the event of mains failure or load transfer from inverter to bypass and vice-versa. The
corresponding LED-indicators will change colours from green (normal) to red (warning).
The LED's LINE 1 (rectifier) and LINE 2 (bypass) indicate the availability of the mains power supply.
The LED's INVERTER and BYPASS if green indicate which of the two is supplying power to the critical load.
When the battery is supplying the load due to mains failure the LED-indicator BATTERY is flashing.
The LED-indicator ALARM is a visual indication of any internal or external alarm condition. At the same time an
audible alarm will be activated.
INDICATOR
INDICATOR STATUS
ALARM
OFF
RED
LINE 1
GREEN
RED
LINE 2
GREEN
RED
OFF
BY-PASS
GREEN
OFF
INV
GREEN
RED
OFF
BATTERY
GREEN
RED
Flashing GREEN

4.1.2.3 Keys

The keys allow the user to operate the UPS to perform settings and adjustments, to start-up and shutdown the
UPS, to monitor on the LCD display the voltages, currents, frequencies and other values.
KEYS
FUNCTION
ON/OFF
Serve to switch-on (press both keys simultaneously), or shutdown the UPS (press both keys
ON/OFF
simultaneously)
UP ()
Move upwards through the menu
DOWN ()
Move downwards through the menu.
Cancel the audible alarm. If the alarm condition was only transient the LED-indicator
RESET
ALARM would also extinguish otherwise it will remain on (red).
ENTER
Confirms a chosen menu item.

4.1.2.4 ON/OFF Start-up and Shutdown Buttons

!
NOTE!
MEANING
No alarm condition
Alarm condition
Mains rectifier available
Mains rectifier not available
Mains bypass available
Mains bypass not OK or not available
UPS is turned off
Load on bypass (Bypass-or Eco-Mode)
Bypass not operating (switched-off)
Load on inverter
Inverter fault or load not transferable to inverter
Inverter not operating (switched-off)
Battery OK
Battery fault or battery is discharged
Battery in discharge or battery fuse open
IN THE CASE THAT THE PARALLEL UPS SYSTEM HAS TO BE TURNED
OFF, THEN BOTH ON/OFF BUTTONS ON ALL UPS MODULES HAVE TO
BE PUSHED. IN THIS CASE THE POWER SUPPLY TO THE LOAD WILL
BE INTERRUPTED
04-3008_S4_ABB_OPMCPDPA-S2_GB_121202
Printed in Switzerland – Modifications reserved
Section-4
Page 3/10 ABB