Options; Introduction; Remote Shut Down - ABB CONCEPTPOWER CLASSIC DPA-50 User Manual

Conceptpower dpa series
Table of Contents

Advertisement

9.1

OPTIONS

9.1.1

Introduction

The CONCEPTPOWER DPA
REMOTE SHUT DOWN FACILITIES
GENERATOR ON FACILITIES
2 CUSTOMER IN FUNTIONS (ON REQUEST)
TEMPERATURE SENSOR FOR TEMP. DEPENDING BATTERY CHARGERING
SOFTWARE FOR AUTOMATIC SHUTDOWN AND MONITORING
SNMP INTERFACES FOR NETWORK MANAGEMENT AND REMOTE MONITORING
9.1.2

Remote SHUT DOWN

The REMOTE SHUT DOWN must use a normally closed contact, which opens to operate the remote shut
down sequence.
The remote shutdown on terminal port X1/1.. X1/2 is located at the bottom of the CONCEPTPOWER DPA
S2 frame on communication card with terminal blocks X1 ...X4. See section 3 / 3.1.2.1 for details.
In order to allow removal, maintenance or testing of any remote shut down facility without disturbing the normal
operation of the UPS, it is recommended that a terminal block, with linking facilities, be installed between the
UPS and the stop button.
1.
Use a screened cable with 1 pair (section of wires 0.5 mm
2.
Connect the cable as shown in Fig. 1.
Fig 1. Drawing of the wiring for the REMOTE SHUT DOWN SWITCH.
TM
S2 is provided with the following accessories:
UPS
Remote shut down
(X1)
X1/1
X1/2
04-3008_S9_ABB_OPMCPDPA-S2_GB_121202
Printed in Switzerland – Modifications reserved
2
) and maximum length of 100 m.
REMOTE SHUT DOWN SWITCH
(N.C. = Normally Closed)
Terminal Block
Section-9
TM
Page 2/6 ABB