Internal Battery Modules Triple Dpa-150 - ABB CONCEPTPOWER CLASSIC DPA-50 User Manual

Conceptpower dpa series
Table of Contents

Advertisement

Section-2
2.3.1.2

Internal Battery Modules TRIPLE DPA-150

TM
In Conceptpower DPA
S2 CLASSIC DPA-50 FRAME there is space for up to 240 x 9Ah internal batteries.
In the drawing below different Battery and System configurations are shown. The batteries may be used as
separate batches for each UPS-Module or they can be used as common batteries for all tree UPS-Modules.
NOTE: For UPS-Systems DPA 30kVA and DPA 50kVA it is allowed to use 40-50 (only even numbers) of 12V-
battery blocks.
NOTE: Set-up the correct number of battery blocks on Control Panel (Menu: Service-Set-Up).
CONCEPTPOWER TRIPLE DPA-150
DPA TRIPLE 150 frame
3x(2x40)x7Ah
Other combination possible : refer to Section 10
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202
Page 12/16 ABB
Printed in Switzerland – Modifications reserved