1.2.5 Environmental Considerations

The UPS must be installed according to the recommendations in this manual. To operate the UPS at peak
efficiency, your installation site should meet the environmental parameters outlined in this manual. Excessive
amount of dust in the operating environment of UPS may cause damage or lead to malfunction. The UPS should
be always protected from the outside weather and sunshine. If you intend to operate the system at an altitude
higher than 1000 meters, contact your local sales or service office for important information about high altitude
operation. The operating environment must meet the weight, airflow, size and clearance requirements specified in
the technical datasheet.
Under no circumstances the UPS should be installed in an airtight room, in the presence of flammable gases, or in
an environment exceeding the specification.
The basic environmental requirements of the UPS system are:
Ambient Temperature Range:
Recommended Operating Range:
Maximum Relative Humidity:
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the bottom
sides and front of the cabinet, and outlets in the rear of the cabinet. You must allow clearance in back of the
cabinet for proper air circulation. Refer to 1.5.2.2 POSITIONING for clearance requirements.

1.2.6 Declaration of Safety conformity and CE marking

The product has the CE marking in compliance with the following European directives:
Low Voltage Directive:
EMC Directive:
Declaration of conformity with UPS harmonized standards and directives EN 62040-1-1 (Safety) and EN 62040-2
(EMC) are available on the web site of the manufacturer.
Safety
Electromagnetic Compatibility
EMC
Performance

1.2.7 Inquiries

Address inquiries about the UPS and battery cabinet to the local office or agent authorized by the manufacturer.
Please note the type code and the serial number of the equipment and contact your nearest agent authorized by
the manufacturer.
The Code and the serial no. are shown on the nameplate see 1.4.4 Nameplate and identification
0 to +40˚C
+20 to +25˚C
95% (non-condensing)
2006/95/EC
2004/108/EC
Product Standards
IEC/EN 62040-1
IEC/EN 62040-2
IEC/EN 62040-3
04-3008_S1_ABB_OPMCPDPA-S2_GB_121202
Printed in Switzerland – Modifications reserved
(32 – 104˚F)
(68 – 77˚F)
Standards
IEC/EN 60950-1
IEC/EN 61000-6-2
IEC/EN 61000-6-4
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6