ABB CONCEPTPOWER CLASSIC DPA-50 User Manual page 44

Conceptpower dpa series
Table of Contents

Advertisement

NOTE:
For UPS-Modules DPA 30kVA, 40kVA and 50kVA use only 40-50 (only even numbers) of 12V-battery blocks.
NOTE: Set-up the correct number of battery blocks on Control Panel (Menu: Service-Set-Up)
Frame: Upgrade DPA 250 with Modules DPA 30 S2 or DPA 50 S2
CBAT DPA-120
A
B
8
5x28Ah
5x28Ah
5x28Ah
7
5x28Ah
5x28Ah
5x28Ah
6
5x28Ah
5x28Ah
5x28Ah
5
5x28Ah
5x28Ah
5x28Ah
4
5x28Ah
5x28Ah
5x28Ah
3
5x28Ah
5x28Ah
5x28Ah
2
5x28Ah
5x28Ah
5x28Ah
5x28Ah
1
F1
F2
Battery Cabinet 120
(3x40)x28Ah
Dimensions (WxHxD)
Weight with trays and w/o
batteries
For detailed information and layout of the battery cabinets please refer to section 10
Examples:
On drawing CBAT DPA-120 (3x40)x28Ah battery blocks are fitted. The "A" column of 40x28Ah belongs to
UPS-1, the "B" column of 40x28Ah belongs to UPS-2 and the "C" column of 40x28Ah belongs to UPS-3.
On drawing CBAT DPA-200 (5x40)x28Ah battery blocks are fitted in the battery cabinet and each UPS-Module
is provided with 40x28Ah.
Depending on the request the batteries may be connected separately for each Module or it is possible to
parallel them together into one common battery for five UPS-modules.
C
F3
mm
kg
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202
Printed in Switzerland – Modifications reserved
CBAT DPA-200
Battery Cabinet 200
(5x40)x28Ah
CBAT DPA-120
730x1975x800
290
CBAT DPA-200
1200x1975x800
410
Page 14/16 ABB