Dc Wiring Instructions; Connections To External Battery Cabinet; Electrical Installation - ABB Conceptpower DPA 500 User Manual

480v ul – modular ups, 100kw – 3 mw
Hide thumbs Also See for Conceptpower DPA 500:
Table of Contents

Advertisement

ANOTHER OPTION FOR THE CENTRALIZED VIEW
5.6.3

DC Wiring Instructions

The UPS-cabinet of the Conceptpower DPA 500 does not have internal batteries; therefore the battery will be external either in cabinets
or in shelves/racks.
5.6.4

Connections to External Battery Cabinet

The DPA 500 UPS uses only externally connected batteries. They may be sealed, maintenance-free lead-acid batteries, flooded lead-
acid cells, or NiCad batteries and are installed and should be connected at the time the UPS is commissioned. The battery charging
system allows adaptation for any of these types of batteries, but must be properly set at installation to the selected battery type. Nominal
battery voltage of 540 volts must be used (refer to Section 11.4 for additional details). Overcurrent protection shall be external to the unit
and supplied by others. The overcurrent protective device should be sized as recommended by the battery system supplier. Wiring shall
be based on overcurrent protective device requirements and recommendations. At a minimum, refer to NEC Section 210-20 (A), Table
310-16 for Allowable Ampacities of Insulated Conductors.
Wire sizing according to
NEC Section 210-20 (A) Table 310-16
Use 167°F (75°C)(minimum) copper or aluminum wire
WARNING
Refer to Section 2.5.2 for wiring connection means
The battery back-up should be sized according to the desired backup time. Note that the backup time is longer if the load is less than the
nominal power rating of the UPS system(s).
If installing a customer-supplied battery system, install the battery system according to the battery and battery system manufacturer's
instructions and all applicable codes and regulations, including the NEC, Article 480.
5.7

Electrical Installation

KEEP OUT OF BATTERY POLES WHICH CONTAIN DANGEROUS DC-VOLTAGES CAUSING FATAL
ACCIDENTS.
DO NOT OPERATE IN CASE OF PRESENCE OF WATER OR MOISTURE. BY OPENING OR REMOVING
DANGER
THE UPS-COVERS YOU RUN RISK OF EXPOSURE TO DANGEROUS VOLTAGES!
SERVICE OF BATTERY SYSTEM SHOULD ONLY BE DONE BY TRAINED SERVICE AND
MAINTENANCE PERSONEL OF THE MANUFACTURER OR AUTHORIZED SERVICE PARTNERS.
Conceptpower DPA 500 480V UL │94-12-043275 A02 21