1.4 Key Features of Conceptpower DPA 500
•
Xtra VFI double conversion mode
•
100 kW rated power module / 500 kW rated power in single frame
•
Extended power range: from 100 kW to 3 MW
•
Unity output power factor (kVA = kW)
•
Double conversion efficiency up to 96 %
•
Efficiency in eco-mode ≥ 99 %
•
Online Swap Modularity (OSM)
•
Online serviceability
•
Top or bottom cable entry (standard)
•
Built-in back-feed protection (standard)
•
Graphical display on system level
•
DPA displays in each module
This Technical Datasheet (TDS) provides all technical specification required by IEC 62040-3, providing
mechanical, electrical and environmental characteristics. It can be used for tendering and end-user
requirements. CONCEPTPOWER DPA 500 is designed to respond to the actual UPS standards which
are:
•
Safety, IEC / EN 62040-1
•
EMC, IEC / EN 62040-2
•
Performance, IEC / EN 62040-3
Modifications reserved
Page 5/25