1.4 Key Features of Conceptpower DPA 500

Xtra VFI double conversion mode
100 kW rated power module / 500 kW rated power in single frame
Extended power range: from 100 kW to 3 MW
Unity output power factor (kVA = kW)
Double conversion efficiency up to 96 %
Efficiency in eco-mode ≥ 99 %
Online Swap Modularity (OSM)
Online serviceability
Top or bottom cable entry (standard)
Built-in back-feed protection (standard)
Graphical display on system level
DPA displays in each module
This Technical Datasheet (TDS) provides all technical specification required by IEC 62040-3, providing
mechanical, electrical and environmental characteristics. It can be used for tendering and end-user
requirements. CONCEPTPOWER DPA 500 is designed to respond to the actual UPS standards which
are:
Safety, IEC / EN 62040-1
EMC, IEC / EN 62040-2
Performance, IEC / EN 62040-3
Modifications reserved