2.8.4
Alarm and saturation values for multidrop mode
Transmitters set to multidrop mode handle saturation and alarm conditions differently.
Alarm conditions
Saturation
2.8.5
Alarm level verification
To verify the transmitter alarm values, perform a loop test and set the transmitter output to
the alarm value (see Tables
protocol" on page
system to a transmitter in an alarm state.
2.8.6
Process alerts
Fast Keys
Process alerts allow the user to configure the transmitter to output a HART message when
the configured data point is exceeded. Process alerts can be set for pressure, temperature,
or both. A process alert will be transmitted continuously if the pressure or temperature set
points are exceeded and the alert mode is ON. An alert will be displayed on a Field
Communicator, or AMS Device Manger status screen. The alert will reset once the value
returns within range.
Note
HI alert value must be higher than the LO alert value. Both alert values must be within the
pressure or temperature sensor limits.
Field Communicator
To configure the process alerts with a Field Communicator, perform the following
procedure:
1.
2.
3.
4.
Configuration
www.aotewell.com
Primary variable is sent with a status bit set
Percent of range follows primary variable
Temperature is sent with a status bit set
Primary variable is sent normally
Temperature is sent normally
2-1
and
18). This feature is also useful in testing the reaction of the control
1, 4, 3, 4
From the HOME screen, follow the Fast Key sequence listed.
Select 3, Config Press Alert to configure the pressure alert.
Select 4, Config Temp Alert to configure the temperature alerts.
Use the right arrow key to configure the HI and LO alert values.
Use the left arrow to move back to the process alert menu.
Select 1, Press Alert Mode to turn on the pressure alert mode.
Select 2, Temp Alert Mode to turn on the temperature alert mode.
sales@aotewell.com
2-2
on
page
12, and
"Advanced functions for HART
Industry Automation
Configuration
September 2016
15