2.8.3
Alarm and saturation levels for burst mode
Transmitters set to burst mode handle saturation and alarm conditions differently.
Alarm conditions
Saturation
14
www.aotewell.com
Right click on the device, select Device Configuration,
Select Alarm/Saturation Levels,
Select Alarm Levels from the menu
Select Next after setting the control loop to manual.
Select Next after acknowledging the current alarm levels.
Select the desired alarm settings: NAMUR, Rosemount, Other
If Other is selected, enter desired HI Value and LO Value custom values.
Select Next to acknowledge new alarm levels.
Select Next to acknowledge the loop can be returned to automatic control.
Select Finish to acknowledge the method is complete.
Right click on the device, select Device Configuration, then select
Alarm/Saturation Levels, then Alarm Levels from the menu
Select Saturation Levels.
Repeat
Step 5
-
11
to configure saturation levels.
Analog output switches to alarm value
Primary variable is burst with a status bit set
Percent of range follows primary variable
Temperature is burst with a status bit set
Analog output switches to saturation value
Primary variable is burst normally
Temperature is burst normally