Quick Start Guide
00825-0100-4022, Rev FA
September 2016
Rosemount
4600 Oil & Gas
Panel Pressure Transmitter

Advertisement

loading

Summary of Contents for Emerson Rosemount 4600

  • Page 1 Quick Start Guide 00825-0100-4022, Rev FA September 2016 ™ Rosemount 4600 Oil & Gas Panel Pressure Transmitter...
  • Page 2 Quick Start Guide NOTICE NOTICE This guide provides basic guidelines for the Rosemount 4600 Oil & Gas Panel Pressure Transmitter. It does not provide instructions for diagnostics, maintenance, service, troubleshooting, explosion-proof, flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 4600 Reference Manual for more instruction.
  • Page 3 3. Connect the green lead to panel ground. The figure below shows the wiring connections necessary to power a Rosemount 4600 and enable communications with a hand-held Field Communicator. Figure 1. Rosemount 4600 Field Wiring A. Rosemount 4600 D. I/A card B.
  • Page 4 September 2016 Quick Start Guide 2.1 Power supply The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included.
  • Page 5 Quick Start Guide September 2016 Table 1. Field Communicator Fast Key Sequence Function Fast Key sequence Digital To Analog Trim (4-20 mA Output) 1, 2, 3, 2, 1 Field Device Information 1, 4, 4, 1 Loop Test 1, 2, 2 Lower Sensor Trim 1, 2, 3, 3, 2 Message...
  • Page 6 Quick Start Guide 4.0 Trim the transmitter Note ™ Transmitters are shipped from Emerson Process Management fully configured per request or by the factory default of full scale (span = upper range limit.) 4.1 Zero trim A zero trim is a single-point adjustment to compensate mounting position and sealed gauge pressure effects.
  • Page 7 Quick Start Guide September 2016 5.0 Safety Instrumented Systems The following section applies to Rosemount 4600 Transmitters used in SIS applications. Note Transmitter output is not safety-rated during the following: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during transmitter configuration and maintenance activities.
  • Page 8 EmersonProcess.com/Rosemount/Safety-Products/Equipment-List. in the event that an error is found in the safety functionality. Reference Table 1 for the Fast Keys to perform a Loop Test, Analog Output Trim, or Sensor Trim. See the Rosemount 4600 Reference Manual for additional information. Proof test This proof test will detect 90 percent of DU failures not detected by the Rosemount 4600 automatic diagnostics.
  • Page 9 Failure rate data The FMEDA report includes failure rates. This report is available at EmersonProcess.com/Rosemount. Rosemount 4600 safety failure values Safety accuracy: 2.0% Safety response time- 1.5 seconds Product life 50 years – based on worst case component wear-out mechanisms – not based on wear-out process wetted materials.
  • Page 10 September 2016 Quick Start Guide 7.0 Product Certifications Rev 1.3 7.1 European directive information A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at EmersonProcess.com/Rosemount.
  • Page 11 Quick Start Guide September 2016 I6 Canada Intrinsic Safety Certificate: 1384913 Standards: CSA Std C22.2 No. 25-1966; CSA Std C22.2 No. 30-M1986; CAN/CSA-C22.2 No. 94-M91; CSA Std C22.2 No. 142-M1987; CAN/CSA-C22.2 No. 157-92; CSA Std C22.2 No. 213-M1987; CAN/CSA-E79- 0-95; CAN/CSA- E79-1-95; CAN/CSA- E79-11-95; ANSI/ISA No.
  • Page 12 The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime. 2. The Rosemount 4600 Transmitter is provided with a permanently connected unterminated cable. The free end of the cable shall be connected using a suitable junction box, e.g.
  • Page 13 Quick Start Guide September 2016 Figure 5. Rosemount 4600 Declaration of Conformity...
  • Page 14 September 2016 Quick Start Guide...
  • Page 15 Quick Start Guide September 2016...
  • Page 16 September 2016 Quick Start Guide Rosemount 4600 China RoHS List of Rosemount 4600 Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6)
  • Page 17 Quick Start Guide September 2016...
  • Page 18 Middle East and Africa Regional Office Standard Terms and Conditions of Sale can be found at Emerson.com/en-us/pages/Terms-of-Use.aspx Emerson Process Management The Emerson logo is a trademark and service mark of Emerson Emerson FZE P.O. Box 17033, Electric Co. Jebel Ali Free Zone - South 2...