ADD DEVICE TO SOFTWARE

3.7.3 Configure Ethernet connection

You connect the Ethernet cable, define a site in the software, then add the relay as a device for the site. The computer and
UR device must be on the same subnet.
1.
Connect the Ethernet network cable to the Ethernet port on the back of the device.
2.
Start the EnerVista UR Setup software, or in EnerVista Launchpad select the UR device to start the software.
3.
Click the Device Setup button. The window opens.
4.
Click the Add Site button. A new category is added. Enter a site name in the Site Name field. Optionally add a short
Description of the site. This example uses "Location 1" as the site name.
5.
Click the Add Device button. A new device is added.
6.
Enter a name in the Device Name field, up to 15 characters, and optionally add a Description of the site. The Color is
for the text in the device list in the Online Window.
3
7.
Select "Ethernet" from the Interface drop-down list. This displays a number of interface parameters that must be
entered for Ethernet functionality.
8.
Enter the relay IP Address, which can be viewed on the device front panel under
COMMUNICATIONS  NETWORK  IP ADDRESS
clicking the Read Order Code button.
9.
Enter the relay Slave address and Modbus Port address values from the settings in the front panel
PRODUCT SETUP  COMMUNICATIONS MODBUS PROTOCOL
10. If using a gateway to connect to the device, select Yes from the drop-down list.
11. Click the Read Order Code button to connect to the B30 device and upload the order code. If the device was entered
already, a message displays "Device 'x' is also using IP address...." If a communications error occurs, ensure that the
values entered in the previous steps correspond to the relay setting values, and also ensure that the same IP address
3-64
Figure 3-67: Configuring Ethernet communication
. Once the IP address is entered, try to load automatically the fields by
SETTINGS  PRODUCT SETUP 
menu.
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
SETTINGS 