PRODUCT SETUP
Security
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup > Security.
SecGSAL1.SecDataClr.ctlModel
5
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model that clients must use to clear security data via commands to
SecGSAL1.SecDataClr. "sbo" here is select-before-operate.
SecGSAL1.OpCntRs ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model that clients must use to clear security data via commands to SecGSAL1.OpCntRs.
"sbo" here is select-before-operate.
Demand
Deadband parameters of measured values related to the Demand metering are configured here.
Energy
Deadband parameters of measured values related to the Energy metering are configured here.
Real Time Clock
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup > Real Time Clock.
5-86