GE B30 Instruction Manual page 243

Bus differential system
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed metered value. It can be used to provide for leading
character spacing of the display value.
For example, setting the number to 2 displays 00.000[V] and setting it to 3 displays 000.000[V].
Number of Decimals
Range: 0 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed metered value. For example, setting the number to 1
displays 0.0 and setting it to 2 displays 0.00.
5.3.3.4 Single-line diagram editor
The path is Settings > Product Setup > Graphical Panel > Single Line Diagram Editor. Use is explained in the Interfaces
chapter.
5.3.3.5 Annunciator editor
The annunciator editor is used to create annunciator content for the graphical front panel, including alarms and actual
values. Use is explained in the Interfaces chapter.
The path is Settings > Product Setup > Graphical Panel > Annunciator Editor.
To add an alarm, access the Annunciator Editor, configure the Layout and Page Name, configure the alarm or actual value,
set the text and color, then save. On the graphical front panel, view the content by pressing the Annunciator Tab
pushbutton at the bottom of the Home page. (Alarms do not display automatically.) Acknowledge or reset the alarm by
navigating to it with the arrow pushbuttons, then pressing the ENTER or RESET pushbutton.
The figure shows alarms for basic functions. The last annunciator page is named Device Alarms. Alarms are set for the
device being offline, Ethernet cable issues, unauthorized access, battery failure, and high ambient temperature. They can
reset themselves when conditions return to normal, except for unauthorized access and temperature monitoring, which
require the alarms to be acknowledged. The self-test error functions, here for Ethernet and battery failures, also have been
enabled under Settings > Product Setup > User-Programmable Self Tests (not shown). When the alarms are triggered,
they display with a red background. An alarm is acknowledged by using the arrow keys on the graphical front panel then
pressing the ENTER button.
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
5
5-35