CHAPTER 5: SETTINGS
The menu is shown on the front panel upon successful login of the Administrator role.
The
setting in this menu is similar to that described in
LOGIN
role.
Passwords are stored in text format. No encryption is applied.
In Device authentication mode, the Observer role does not have a password associated with it. In Server
authentication mode the Observer role requires a password.
If you are locked out of the software, contact GE Grid Solutions for the default password. When using CyberSentry,
the default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role-associated password.
In CyberSentry, password encryption is not supported.
Session settings
SETTINGS  PRODUCT SETUP  SECURITY  SESSION SETTINGS
 SESSION
 SETTINGS
— This setting specifies the number of failed authentications before the device blocks subsequent
SESSION LOCKOUT
authentication attempts for the lockout period. A value of zero means lockout is disabled.
— This setting specifies the period of time in minutes of a lockout period. A value of 0 means that
SESSION LOCKOUT PERIOD
there is no lockout period.
Restore defaults
SETTINGS  PRODUCT SETUP  SECURITY  RESTORE DEFAULTS
 RESTORE DEFAULTS
— This setting is used to reset all the settings, communication, and security passwords. An
LOAD FACTORY DEFAULTS
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
Supervisory
SETTINGS  PRODUCT SETUP  SECURITY  SUPERVISORY
 SUPERVISORY
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
NEW PASSWORD:
CONFIRM PASSWORD:
SETTINGS > PRODUCT SETUP > SECURITY
SESSION LOCKOUT:
3
SESSION LOCKOUT
PERIOD: 3 min
LOAD FACTORY
DEFAULTS: No
DEVICE
AUTHENTICATION: Yes
BYPASS ACCESS:
Disabled
LOCK RELAY:
Disabled
FACTORY SERVICE
MODE: Disabled
 SELF TESTS
Range: 20 alphanumeric characters
Range: 20 alphanumeric characters
except for the factory
Range: 0 to 99
Range: 0 to 9999 minutes
Range: Yes, No
Range: Yes, No
Range: Local, Remote, Local and Remote, Disabled,
Pushbuttons
Range: Enabled, Disabled
Range: Enabled, Disabled
See below