GE B30 Instruction Manual page 260

Bus differential system
Hide thumbs Also See for B30:
Table of Contents

Advertisement

PRODUCT SETUP
5
5-52
DNP VOLTAGE SCALE
FACTOR: 1
DNP POWER SCALE
FACTOR: 1
DNP ENERGY SCALE
FACTOR: 1
DNP PF SCALE
FACTOR: 1
DNP OTHER SCALE
FACTOR: 1
DNP CURRENT DEFAULT
DEADBAND: 30000
DNP VOLTAGE DEFAULT
DEADBAND: 30000
DNP POWER DEFAULT
DEADBAND: 30000
DNP ENERGY DEFAULT
DEADBAND: 30000
DNP PF DEFAULT
DEADBAND: 30000
DNP OTHER DEFAULT
DEADBAND: 30000
DNP TIME SYNC IIN
PERIOD: 1440 min
DNP MESSAGE FRAGMENT
SIZE: 240
DNP OBJECT 1
DEFAULT VARIATION: 2
DNP OBJECT 2
DEFAULT VARIATION: 2
DNP OBJECT 20
DEFAULT VARIATION: 1
DNP OBJECT 21
DEFAULT VARIATION: 1
DNP OBJECT 22
DEFAULT VARIATION: 1
DNP OBJECT 23
DEFAULT VARIATION: 1
DNP OBJECT 30
DEFAULT VARIATION: 1
DNP OBJECT 32
DEFAULT VARIATION: 1
DNP NUMBER OF PAIRED
CONTROL POINTS: 0
DNP TCP CONNECTION
TIMEOUT: 120 s
DNP EVENT TIME BASE:
LOCAL
CHAPTER 5: SETTINGS
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000, 1000000, 10000000, 100000000
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 1 to 10080 min. in steps of 1
Range: 30 to 2048 in steps of 1
Range: 1, 2
Range: 1, 2, 3
Range: 1, 2, 5, 6
Range: 1, 2, 9, 10
Range: 1, 2, 5, 6
Range: 1, 2, 5, 6
Range: 1, 2, 3, 4, 5
Range: 1, 2, 3, 4, 5, 7
Range: 0 to 32 in steps of 1
Range: 10 to 7200 s in steps of 1
Range: UTC, LOCAL
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL

Advertisement

Table of Contents
loading

Table of Contents