GE B30 Instruction Manual page 309

Bus differential system
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
IEC 60870-5-104 is a transmission protocol for network access, specifically for communication between a control station
and substation over a TCP/IP network.
The B30 supports the IEC 60870-5-104 protocol. This protocol is enabled when the
COMMUNICATIONS  PROTOCOL
connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the B30 maintains two
sets of IEC 60870-5-104 data change buffers, ideally no more than two masters actively communicate with the B30 at one
time.
The
IEC ------- DEFAULT THRESHOLD
M_ME_NC_1 analog data. These settings group the B30 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the B30 when any current values change by 15 A, the
setting is set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of measured
value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the B30, the default thresholds are in effect.
The
setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,
IEC REDUNDANCY
two simultaneous connections can be active at any given time.
— To close the port, set the port number to 0. Any change takes effect when the B30 is restarted.
IEC TCP PORT NUMBER
IEC COMMON ADDRESS OF ASDU
— The change takes effect when the B30 is restarted.
IEC CYCLIC DATA PERIOD
B30 devices without CT and VT inputs do not support power metering or energy metering. As such, the
and the
DEFAULT THRESHOLD
inputs.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
IEC COMMON ADDRESS
OF ASDU:
0
IEC CYCLIC DATA
PERIOD: 60 s
IEC CURRENT DEFAULT
THRESHOLD: 30000
IEC VOLTAGE DEFAULT
THRESHOLD: 30000
IEC POWER DEFAULT
THRESHOLD: 30000
IEC ENERGY DEFAULT
THRESHOLD: 30000
IEC PF DEFAULT
THRESHOLD: 1.00
IEC OTHER DEFAULT
THRESHOLD: 30000
IEC REDUNDANCY
ENABLED: No
setting is set to IEC 60870-5-104. The B30 can be used as an IEC 60870-5-104 slave device
settings are used to determine when to trigger spontaneous responses containing
— The change takes effect when the B30 is restarted.
IEC ENERGY DEFAULT THRESHOLD
Range: 0 to 65535 in steps of 1
Range: 1 to 65535 s in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0.00 to 1.00
Range: 0 to 65535 in steps of 1
Range: No, Yes
SETTINGS  PRODUCT SETUP 
IEC CURRENT DEFAULT THRESHOLD
setting do not apply to B30 devices without CT and VT
PRODUCT SETUP
5
IEC POWER
5-101