SPECIFICATIONS
DCMA OUTPUTS
Range:
Max. load resistance:
Accuracy:
2
99% Settling time to a step change:
Isolation:
Driving signal:
Upper and lower limit for the driving signal: –90 to 90 pu in steps of 0.001

2.5.8 Communication protocols

IEC 61850
IEC 61850:
RS232 (Enhanced and standard front panels)
Front port:
USB (Graphical front panel)
Front port:
RS485
1 rear port:
Typical distance:
Isolation:
FIBER ETHERNET PORT
Parameter
Wavelength
Connector
Transmit power
Receiver sensitivity
Power budget
Maximum input power
Typical distance
Full duplex
Redundancy
ETHERNET (10/100 MB TWISTED PAIR)
Modes:
Connector:
SIMPLE NETWORK TIME PROTOCOL (SNTP)
Clock synchronization error:
PRECISION TIME PROTOCOL (PTP)
PTP IEEE Std 1588 2008 (version 2)
Power Profile (PP) per IEEE Standard PC37.238TM2011
Slave-only ordinary clock
Peer delay measurement mechanism
2-30
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
12 kΩ for –1 to 1 mA range
12 kΩ for 0 to 1 mA range
600 Ω for 4 to 20 mA range
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
100 ms
1.5 kV
any FlexAnalog quantity
Supports IEC 61850 Edition 2.0. See the UR Family Communications Guide and its conformance
statements.
19.2 kbps, Modbus RTU
USB 2.0 type B
up to 115 kbps, Modbus RTU, DNP 3, IEC 60870-5-103
1200 m
2 kV, isolated together at 36 Vpk
Fiber type
100 Mb multimode
1310 nm
LC
–20 dBm
–30 dBm
10 dB
–14 dBm
2 km
yes
yes
10 Mb, 10/100 Mb (auto-detect)
RJ45
<10 ms (typical)