GE B30 Instruction Manual page 232

Bus differential system
Hide thumbs Also See for B30:
Table of Contents

Advertisement

PRODUCT SETUP
3.
On the RADIUS server, configure the user accounts. Do not use the five pre-defined roles as user names (Administrator,
Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the
authentication from the device.
4.
In the EnerVista software, choose Server authentication and log in using the user name and password configured on
the RADIUS server for Server authentication login.
5.
After making any required changes, log out.
Pushbuttons (both user-control buttons and user-programmable buttons) located on the front panel can be pressed by an
Administrator or Engineer role. This also applies to the
displayed on the front panel or the Targets panel of the EnerVista software. The
allows these two roles to press it even when they are logged in through the RS232 port and not through the front panel.
To reset the security event log and self-test operands:
1.
Log in as Supervisor (if the role is enabled) or Administrator (if the Supervisor role is disabled) and execute a clear
security command under Commands > Security > Clear Security.
Security events
The security events produced when the CyberSentry option is purchased are sent as sytem log (syslog) messages to a
syslog server, if one is configured. The format is as follows.
Security log
5
— Event identification number (index)
Event Number
— UTC date and time
Date & Timestamp
— 255 chars maximum, but in the security log it is truncated to 20 characters
Username
— Device IP address
IP address
— 16 bit unsigned, of type format F617
Role
Enumeration Role
0
None
1
Administrator
2
Supervisor
3
Engineer
4
Operator
5
Factory
— 16 bit unsigned
Activity Value
Enumeration Description
1
Authentication Failed
2
User Lockout
3
FW Upgrade
4
FW Lock
5
Settings Lock
6
Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7
Clear Oscillography command
8
Clear Data Logger command (not applicable to all UR products)
9
Clear Demand Records command (not applicable to all UR products)
5-24
When changing settings offline, ensure that only settings permitted by the role that performs the
settings download are changed because only those changes are applied.
Event Number
Date &
Timestamp
button, which resets targets, where targets are errors
RESET
RESET
Username
IP address
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
button has special behavior in that it
Role
Activity Value

Advertisement

Table of Contents
loading

Table of Contents