Analog Output 1 - ABB COMMANDER 360 User Manual

Profile controller
Table of Contents

Advertisement

...5 CONFIGURATION MODE

5.8.2 Analog Output 1

tYP1
ANLG
C. 0 2
ANI. A
NONE
C. 0 3
AN1. H
20. 0
C. 0 4
AN1. L
4. 0
•2
C. 0 5
r1. H
100. 0
•2
C. 0 6
r1. L
0. 0
AN2. A
NONE
•1
If the output is assigned to a control output by the control type, the setting displayed cannot be changed – see
Section 5.2, Basic Configuration/Control Output Type.
•2
Not applicable if analog output 1 is assigned to a control output.
74
Analog Output 1 (ao1) Assignment Source
•1
Select the source required to activate Analog Output 1
See Rear Fold-out/ Table C – Analog Sources.
Analog Output 1 (ao1) Electrical High
The maximum current output required for the analog output.
[0.0 to 22.0mA]
Analog Output 1 (ao1) Electrical Low
The minimum current output required for the analog output.
[0.0 to 22.0mA]
Retransmission 1 Engineering High
The engineering range value at which maximum output is required.
[In engineering units]
Retransmission 1 Engineering Low
The engineering range value at which minimum output is required.
[In engineering units]
Continued...