ABB COMMANDER 360 User Manual page 49

Profile controller
Table of Contents

Advertisement

...4.3 Level 3 – Set Points
•1
3. 0 8
C. r tO
1. 0 00
•1
3. 0 9
C. b IA
0
3. 1 0
r. r tE
OFF
LEV3
SEt. P
•1
Displayed only if the Cascade template is selected – see Section 5.2, Basic Configuration/ Template
Application.
Cascade Set Point Ratio
In automatic mode, the slave set point value is:
(ratio x master output) + bias.
[0.001 to 9.999]
Cascade Set Point Bias
[In engineering units]
Ramp Rate
[1 to 9999 engineering units per hour, or OFF]
The Ramping Set Point facility can be used to prevent a large disturbance
to the control output when the set point value is changed. The rate set
applies to both the local and the remote set points.
PV
300
200
100
0
1 Hour
* e.g. Ramp Rate = 200 Increments/Hour
Return to top of page.
4 SET UP MODE...
Displayed Local Set Point Value
Actual (Ramping) Set Point Value
used by PID Algorithm*
8
3.08...3.10
Time