...3.4 Ramp/Soak Profile Control
r. 1 7
SKP. E
NO
r. 1 8
t. A d. E
NO
r. 1 9
P. r EC
A
•1
r. 2 0
P. P Er
0. 0
r. 2 1
SSSP
NO
r. 2 2
rEtO
OFF
LEVr
P. C tL
•1
Not displayed if power down recovery option d is selected.
Front Panel Segment Skip Enable
– Operator level segment skip forwards & backwards enabled
Fd. b K
– Operator level segment skip backwards enabled
bK
– Operator level segment skip forwards enabled
Fd
– Operator level segment skip disabled
NO
Front Panel Segment Time Adjustment Enable
Operator level time increment and decrement enabled
UP. d N
Operator level time decrement enabled
dN
Operator level time increment enabled
UP
Operator level time adjust disabled
NO
Power-down Recovery Option
Select the profile restart position when power is restored after a failure and
the
Power Down Time Period
– Start of the current program, profile set to operator hold mode
A
– start of the current segment, profile set to operator hold mode
b
– profile position unchanged, profile set to operator hold mode
C
– calculated position in profile had the power not failed
d
Note. Option d does not work with segments of more than 24 hours
duration or if the power down time is greater than 24 hours. When power
is restored, the profile is set to operator hold mode and the profile position
is unchanged.
Power-down Time Period (Power-down recovery options A, b & C)
Set the time period during which, if power is restored, the profile continues
from the point at which power failed. If the
the
Power-down Recovery Option
[0.0 to 99.9 minutes]
Self-Seeking Set Point
YES
Enable self-seeking set point
NO
Disable self-seeking set point
When enabled, the controller uses the current process variable value as
the starting point of the first profile segment – see Section 3.2.4.
Retort Function
See Section 3.2.5
Disable retort function
OFF
Complete soak segment
A
Repeat soak segment
b
Return to the top of the Profile Control Page.
3 PROFILES...
(see below) has expired. See Section 3.2.3.
Power-down Time
, selected above, is invoked.
r.17...r.22
is exceeded
35