...4.2 Level 2 – Tune
•1
2. 0 5
Pb-1
100. 0
•1
2. 0 6
Pb-2
•2
100. 0
•3
2. 0 8
Pb-4
100. 0
2. 0 9
IAt. 1
OFF
•2
2. 1 0
IAt. . 2
OFF
•3
2. . 1 2
IAt. 4
OFF
2. 1 3
drV1
OFF
•1
Heat/cool outputs use a common proportional band. The default is 'Pb-1'.
•2
Only displayed if the cascade template or a tune parameter source is selected – see Section 5.2, Basic
Configuration/ Template Application and Section 5.6, Control Configuration/ Tune Parameter Source.
•3
Only displayed if a tune parameter source is selected – see Section 5.6, Control Configuration/ Tune
Parameter Source.
Proportional Band 1
Enter the value for Proportional Band 1.
[0.1% to 999.9%]
'Pb-1' is the default proportional band and is the proportional band for the
master controller if a cascade template is selected – see Section 5.2,
Basic Configuration/ Template Application.
Proportional Band 2, 3 and 4
Enter the value for Proportional Band 2, 3 and/or 4.
[0.1% to 999.9%]
'Pb-2' is the proportional band for the slave controller if a cascade
template is selected – see Section 5.2, Basic Configuration/ Template
Application.
Integral Action Time 1
[1 to 7200 seconds or 'OFF']
'IAt.1' is the default integral action time and is the integral action time for
the master controller if a cascade template is selected – see Section 5.2,
Basic Configuration/ Template Application.
Integral Action Time 2, 3 and 4
[1 to 7200 seconds or 'OFF']
'IAt.2' is the integral action time for the slave controller if a cascade
template is selected – see Section 5.2, Basic Configuration/ Template
Application.
Derivative Action Time 1
[0.1 to 999.9 seconds or 'OFF']
'drV.1' is the derivative action time for the master controller if a cascade
template is selected – see Section 5.2, Basic Configuration/ Template
Application.
Continued on next page.
4 SET UP MODE...
2.05...2.13
8
41